STAD

03-06-2016

The STAD balancing valve delivers accurate hydronic performance in an impressive range of applications. Ideally suited for use on the secondary side in heating and cooling systems, and tap water systems.

Image


Balancing valve DN 15-50

The STAD balancing valve delivers accurate hydronic performance in an impressive range of applications. Ideally suited for use on the secondary side in heating and cooling systems, and tap water systems.

 

Key features

 

Handwheel

Equipped with a digital read-out, the handwheel ensures accurate and straightforward balancing. Positive shut-off function for easy maintenance.

 

Self-sealing measuring points

For simple, accurate balancing.

 

AMETAL®

Dezincification resistant alloy that guarantees a longer valve lifetime, and lowers the risk of leakage.


Technical description

 

Application:

Heating and cooling systems
Tap water systems

 

Functions:

Balancing
Pre-setting
Measuring
Shut-off
Draining (optional)

 

Dimensions:

DN 10-50

 

Pressure class:

PN 20

 

Temperature:

Max. working temperature: 120°C.
For higher temperatures (max. 150°C), please contact the nearest sales office. NOTE! DN 25-50 with smooth ends max working temperature 120°C.
Min. working temperature: -20°C

 

Material:

The valves are made of AMETAL®
Seat seal: Stem with EPDM O-ring
Spindle seal: EPDM O-ring
Handwheel: Polyamide and TPE.
Smooth ends:
Nipple: AMETAL®
Sealing (DN 25-50): EPDM O-ring
AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.

 

Marking:

Body: TA, PN 20/150, DN and inch size.
Handwheel: Valve type and DN.

Our Partners